Remote Module Setup

BESTCOMSPlus Navigation Path: Settings Explorer, System Parameters, Remote Module Setup

Front Panel Navigation Path: Settings > System Settings > Remote Module Setup

DGC-2020HD controllers are capable of communicating with up to four contact expansion modules
(CEM-2020s) and up to four analog expansion modules (AEM-2020s) on a single network.

To set up an optional CEM-2020, select Enable, input the appropriate J1939 address, and select the
appropriate number of outputs available to the module. The low current module (CEM-2020) provides 24
contact outputs and the high current module (CEM-2020H) provides 18 contact outputs.

For optional AEM-2020 setup, select Enable, input the appropriate J1939 address, and input the
expected serial number. Expected serial numbers are used by the DGC-2020HD to determine which
input/output points belong to a module when multiple modules are present. An AEM-2020 Not Configured
pre-alarm occurs if the expected serial number does not match the serial number detected on the General
Settings, Device Info screen.

Figure 170 illustrates the BESTCOMSPlus Remote Module Setup screen.

Figure 170. Settings Explorer, System Parameters, Remote Module Setup

Crank Settings

BESTCOMSPlus Navigation Path: Settings Explorer, System Parameters, Crank Settings

Front Panel Navigation Path: Settings > System Parameters > Crank Settings

Crank settings consist of pre-start, restart, cranking, crank disconnect, and cool down. These settings are
described in the paragraphs below.

Figure 171 illustrates the BESTCOMSPlus Crank Settings screen. Settings are listed in Table 78.