Figure 129. Settings Explorer, Alarm Configuration, Pre-Alarms



Table 51. Settings for Pre-Alarms

Locator

Setting

Range

Increment

Unit

High Battery Voltage Settings

A

Threshold V

0 or 12 to 32

0.1

volts

B

Threshold Per Unit

based on nominal

n/a

n/a

Low Battery Voltage Settings

C

Threshold V

0 or 6 to 28

0.1

volts

D

Threshold Per Unit

based on nominal

n/a

n/a

E

Activation Delay

0 to 10

0.1

seconds

Weak Battery Voltage Settings

F

Threshold V

0 or 4 to 28

0.1

volts

G

Threshold Per Unit

based on nominal

n/a

n/a

H

Activation Delay

0 to 10

0.1

seconds

High Fuel Level Settings

I

Threshold

0 to 150

1

%

J

Activation Delay

0 to 30

1

seconds

Low Fuel Level Settings

K

Threshold

10 to 100

1

%

Reporting and Alarms