Figure 129. Settings Explorer, Alarm Configuration, Pre-Alarms
Table 51. Settings for Pre-Alarms
Locator
Setting
Range
Increment
Unit
High Battery Voltage Settings
A
Threshold V
0 or 12 to 32
0.1
volts
B
Threshold Per Unit
based on nominal
n/a
n/a
Low Battery Voltage Settings
C
Threshold V
0 or 6 to 28
0.1
volts
D
Threshold Per Unit
based on nominal
n/a
n/a
E
Activation Delay
0 to 10
0.1
seconds
Weak Battery Voltage Settings
F
Threshold V
0 or 4 to 28
0.1
volts
G
Threshold Per Unit
based on nominal
n/a
n/a
H
Activation Delay
0 to 10
0.1
seconds
High Fuel Level Settings
I
Threshold
0 to 150
1
%
J
Activation Delay
0 to 30
1
seconds
Low Fuel Level Settings
K
Threshold
10 to 100
1
%
Reporting and Alarms
DGC-2020HD