Type tests, Shock, Vibration – Basler Electric DGC-2020HD User Manual

Page 336: Ignition system, Halt (highly accelerated lift testing), Environment, Temperature, Humidity, Ul approval (cem-2020 only), Ul approval (cem-2020h only)

Advertising
background image

326

9469300990 Rev B

CEM-2020

DGC-2020HD

Type Tests

Shock

Withstands 15 G in 3 perpendicular planes.

Vibration

Swept over the following ranges for12 sweeps in each of three mutually perpendicular planes with each
15-minute sweep consisting of the following:
5 to 29 to 5 Hz ......................................... 1.5 G peak for 5 minutes
29 to 52 to 29 Hz .....................................

0.036” Double Amplitude for 2.5 minutes

52 to 500 to 52 Hz ................................... 5 G peak for 7.5 minutes

Ignition System

Tested in close proximity to an unshielded, unsuppressed Altronic DISN 800 ignition system.

HALT (Highly Accelerated Lift Testing)

HALT is used by Basler Electric to prove that our products will provide the user with many years of
reliable service. HALT subjects the device to extremes in temperature, shock, and vibration to simulate
years of operation, but in a much shorter period span. HALT allows Basler Electric to evaluate all possible
design elements that will add to the life of this device. As an example of some of the extreme testing
conditions, the CEM-2020 was subjected to temperature tests (tested over a temperature range of

–80°C

to +130

°C),

vibration tests (of 5 to 50 G at +25

°C), and temperature/vibration tests (tested at 10 to 20 G

over a temperature range of

–60°C to +100°C). Combined temperature and vibration testing at these

extremes proves that the CEM-2020 is expected to provide long-term operation in a rugged environment.
Note that the vibration and temperature extremes listed in this paragraph are specific to HALT and do not
reflect recommended operation levels. These operational ratings are included in this section.

Environment

Temperature

Operating.................................................

–40 to +70°C (–40 to +158°F)

Storage ...................................................

–40 to +85°C (–40 to +185°F)

Humidity

Meets IEC 68-2-38.

UL Approval (CEM-2020 Only)

“cRUus” recognized to UL Standard 6200 & CSA Standard C22.2 No. 14.

UL Approval (CEM-2020H Only)

UL recognized to UL Standard 6200.

CSA Certification

CSA certified to Standard C22.2 No.14.

NFPA Compliance

Complies with NFPA Standard 110, Standard for Emergency and Standby Power.

CE Compliance

This product complies with the requirements of the following EC Directives:
LVD 2006/95/EC

EN 50178