DPF Status and Pre-Alarms

The DGC-2020HD receives DPF status information which is broadcast from the engine ECU in various
Parameter Group Numbers (PGN) and Suspect Parameter Numbers (SPN). This information is displayed
on the front panel and in BESTCOMSPlus, via DPF related pre-alarms. The J1939 parameters and the
resulting DGC-2020HD pre-alarms are summarized in the following paragraphs.

PGN 64892 (0xFD7C) Diesel Particulate Filter Control 1

o

SPN 3697, Diesel Particulate Filter Lamp Command

REGEN REQUIRED Pre-Alarm: When SPN 3697 has a value of
1 or 4 indicating the DPF lamp is on, the DGC-2020HD will
annunciate a pre-alarm with text of REGEN REQUIRED. The
symbol, shown to the right, will accompany the text when the pre-
alarm appears on the DGC-2020HD front panel.

o

SPN 3698, Exhaust System High Temperature Lamp Command

HIGH EXHAUST TEMP Pre-Alarm: When SPN 3698 has a value
of 1 indicating the high exhaust temperature lamp is on, the DGC-
2020HD will annunciate a pre-alarm with text of HIGH EXHAUST
TEMP. The high exhaust temperature symbol, shown to the right,
will accompany the text when the pre-alarm appears on the DGC-
2020HD front panel.

o

SPN 3703 Diesel Particulate Filter Active Regeneration Inhibited Due to Inhibit Switch

REGEN INHIBITED Pre-Alarm: When SPN 3703 has a value of 1
indicating that regeneration is inhibited due to the inhibit switch
being set, the DGC-2020HD annunciates a pre-alarm with text of
REGEN INHBTD. The regeneration inhibited symbol, shown to the
right, will accompany the text when the pre-alarm appears on the
DGC-2020HD front panel.

o

SPN 3703 Diesel Particulate Filter Status

SPN 3703 indicates that regeneration is required at the lowest level, moderate level, or most
severe level. The DGC-2020HD uses this parameter for Soot Level Pre-alarms which are
described in the following paragraphs.

Soot Level Annunciation

The DGC-2020HD annunciates Soot Level pre-alarms which are described in the following
paragraphs.

o

SOOT LEVEL HIGH Pre-Alarm

This pre-alarm is annunciated when one of the following occurs.

 A DTC is received with SPN 3719 (Diesel Particulate Filter Soot Load Percent) with

FMI = 15 (Data Valid But Above Normal Operating Range Least Severe Level)

 SPN 3703 (Diesel Particulate Filter Status) is received with a value of 001

(regeneration is needed – lowest level)

The pre-alarm text is SOOT LVL HI.

The symbol, shown to the right, accompanies the text when the pre-alarm
appears on the DGC-2020HD front panel.

o

SOOT LEVEL MODERATELY HIGH Pre-Alarm

This pre-alarm is annunciated when one of the following occurs.

 A DTC is received with SPN 3719 (Diesel Particulate Filter Soot Load Percent) with

FMI = 16 (Data Valid But Above Normal Operating Range Moderately Severe Level)

Exhaust Treatment