360

9469300990 Rev B

Figure 229. 46 Time Characteristic Curve

Note

Curves are shown extending further to the left than they will in practice. Curves stop at pickup
level. For example, if the user selects 5A FLC with a pickup setting of 0.5 A, the per-unit pickup
is 0.1 A. The relay will not pick up at less than 0.1 pu I2 for these settings.

Time Curve Characteristics

DGC-2020HD