9469300990 Rev B

343

Relay Equation

When the 46 function is used, the relay uses the K factor (i.e., 46 time dial setting), 46 minimum pickup
setting, and generator full-load current to create a constant Z (see Equation 13).

𝑍 = 46 𝑇𝑖𝑚𝑒 𝐷𝑖𝑎𝑙 �

𝐼

𝑁𝑜𝑚 𝑆𝑒𝑡𝑡𝑖𝑛𝑔

46 𝑃𝑖𝑐𝑘𝑢𝑝 𝑆𝑒𝑡𝑡𝑖𝑛𝑔�

2

Equation 13

The time to trip equation used in the relay is:

𝑇

𝑇

=

𝑍

𝑀

2

+ 0.028 𝑠𝑒𝑐𝑜𝑛𝑑𝑠

Equation 14

where:

𝑀 =

𝑀𝑒𝑎𝑠𝑢𝑟𝑒𝑑 𝐼

2

46 𝑃𝑖𝑐𝑘𝑢𝑝 𝑆𝑒𝑡𝑡𝑖𝑛𝑔

Equation 15

which, when M > 1, reduces to:

𝑇

𝑇

= 46 𝑇𝑖𝑚𝑒 𝐷𝑖𝑎𝑙 �

𝐼

𝑁𝑜𝑚 𝑆𝑒𝑡𝑡𝑖𝑛𝑔

𝐼

2

𝑀𝑒𝑎𝑠𝑢𝑟𝑒𝑑�

2

Equation 16

DGC-2020HD

Time Curve Characteristics

Advertising