213

Name

Description

Symbol

Emergency
Stop

True when the Emergency Stop button has been
pressed.

Fuel Leak
Detect

True when the Fuel Leak Detect function is
configured as an alarm and the activation delay
has expired.

Global Alarm

True when one or more alarms are set.

Global Sender
Fail

True when one or more of the Sender Fails are
configured as alarms and are true.

GOV Output
Out of Range

True when GOV Output is the selected
parameter, Out of Range Alarm Type is set to
Alarm, and the threshold has been exceeded.

High Coolant
Temp

True when the High Coolant Temp Alarm settings
have been exceeded.

Low Coolant
Level

True when the Low Coolant Level function is
configured as an alarm and the activation delay
has expired. In addition, true when CAN bus is
enabled and the Low Coolant Level Alarm
threshold has been exceeded.

Low Fuel Level

True when the Low Fuel Level Alarm settings
have been exceeded.

Low Oil
Pressure

True when the Low Oil Pressure Alarm settings
have been exceeded.

LS Output Out
of Range

True when LS Output is the selected parameter,
Out of Range Alarm Type is set to Alarm, and the
threshold has been exceeded.

Mains Fail
Transfer Failed

True when a mains fail transfer fail pre-alarm
occurs. The pre-alarm occurs when the DGC-
2020HD is configured for mains fail transfers, but
has not transferred to the generator from the
utility before the Mains Fail Max Transfer Time
has expired. It remains true until the pre-alarm is
cleared by pressing the Reset button on the front
panel.

Overcrank

True when an Overcrank condition exists.

Overspeed

True when the Overspeed Alarm settings have
been exceeded.

Unexpected
Shutdown

True when the metered engine speed (RPM)
unexpectedly drops to zero (0) while the engine is
running.

Configurable Protection

Threshold x

True when the Alarm Configuration is set to
Alarm and the threshold has been exceeded.

Generator Protection

Frequency

True when the 81-x element is configured as an
alarm and has tripped.

DGC-2020HD

BESTlogic