Metric Pressure Units

When system units are displayed in Metric, this setting allows engine oil pressure to be displayed in either
bar or kPa/MPa.

System Breaker Configuration

Select the appropriate breaker control configuration using the System Breaker Configuration setting. In
BESTCOMSPlus, a one-line diagram is provided for each breaker configuration to aid in proper selection.
Refer to the Breaker Management chapter for details on system breaker configurations.

Generator, Bus 1, and Bus 2 Labels

Each bus can be programmed with a text label describing its use. Up to 64 alphanumeric characters are
accepted. This label appears in BESTCOMSPlus to aid in ease of configuration and programming.

Figure 166. Settings Explorer, System Parameters, System Settings

Table 76. Settings for System Settings

Locator

Setting

Range

Increment

Unit

A

System Type

Single Generator or

Multiple Generator

n/a

n/a

B

Number Fly Wheel Teeth

1 to 500

0.1

n/a

C

Power Up Delay

0 to 60

1

seconds

DGC-2020HD

Configuration