232

9469300990 Rev B

Name

Description

Symbol

RDP
Programmable
Alarm x

When the Set input is true, this element illuminates the Fuel
Leak/Sender Failure LED on the Remote Display Panel RDP-
110. When this element is connected in logic, it overrides all
other commands to the LED. Otherwise, the LED operates as
normal.

RDP
Programmable
Pre-Alarm x

When the Set input is true, this element illuminates the Battery
Overvoltage LED on the Remote Display Panel RDP-110.

When

this element is connected in logic, it overrides all other
commands to the LED. Otherwise, the LED operates as normal.

Reset

When the Set input is true, generator protection elements 78
and 81 are reset as well as all protection elements associated
with Bus 1 and Bus 2. Reset can also be accomplished by
pressing the Reset button on the front panel of the DGC-
2020HD.

Reset Bus 1

When the Set input is true, all protection associated only with
Bus 1 is reset.

Reset Bus 2

When the Set input is true, all protection associated only with
Bus 2 is reset.

Run Inhibit

When the Inhibit input is true, the DGC-2020HD is prevented
from starting and running the generator, regardless of any
condition that would normally cause the generator to run. If this
element is false and there is any condition in effect which will
cause the generator to run, the DGC-2020HD will start and run
the generator.

Run Mode

When the Set input is true, and the DGC-2020HD is in OFF
mode, the DGC-2020HD will switch to RUN mode. This is a
pulsed input. It does not need to be held after the desired mode
switch has occurred.

Run Output

This element is used to drive the run output relay from logic
when the Run Output Relay configuration is set to
“Programmable”. When the Run Output Relay configuration is
set to “Programmable”, the run relay will not close unless logic is
used to drive this element. When the Run Output Relay
configuration is set to “Predefined”, the run relay is closed
according to the predefined run functionality of the DGC-
2020HD. When the “Predefined” functionality is selected, the
relay will not respond to this element.

Run with Load

The Start input starts the generator and closes the Gen breaker.
The Stop input stops the generator and opens the Gen breaker.
The DGC-2020HD only responds to this logic element when in
AUTO mode.

Sequenced
System Startup

When the Start input is true, this element starts a sequence
system when no machines are running. This starts the first unit
in a multiple unit system based on the sequencing criterion.

BESTlogic

Plus

DGC-2020HD

Advertising