9469300990 Rev B

375

Fault

Code

String

Description

506

AL LOW STARTER VOLTS

Battery voltage is too low for starting.

507

AL POM ERROR

A general POM error has been detected.

508

AL WRONG POM ID

POM sends a different identification number (ID) than expected.

509

AL CHECK POM FUSE

Check POM fuse.

510

AL OVERRIDE APPLIED

Override applied.

515

STARTER NOT ENGAGED

Starter of POM could not be engaged.

543

MULTIPLE FDH SLAVES

There is more than one device which is configured as Backup for
FDH-Functionality.

544

CONFIGURATION CHANGED

Gets active in case of changing system configuration e.g. by
changing ECU- or SAM-Device. Remains until undo procedure or
data is transferred by a valid maintenance case. Is cancelled
automatically.

549

AL PWR CUTOFF STR

This is the alarm from the function Emergency Stop Counter. ECU
power was disconnected while the engine was still running. This
could lead to a possible overpressure in the high pressure system
which might damage the engine.

555

AL CALL FIELD SERVICE

Gets active in case of completing a maintenance-case which
manipulates Engine-Parameters. Remains also after switching on-
off ECU until a valid release code is entered via Display- and
Button-Control of SAM-Device. Release Code is available via
Internet by a special procedure.

576

AL ESCM OVERRIDE STR

Exceeding of the corrected current MCR - odr DBR/MCR value.

594

AL L1 PRV 1 DEFECT STR

Yellow alarm pressure relief valve first rail.

595

AL L2 PRV 1 DEFECT STR

Red alarm pressure relief valve first rail.

598

AL L1 PRV 2 DEFECT STR

Yellow alarm pressure relief valve second rail.

599

AL L2 PRV 2 DEFECT STR

Red alarm pressure relief valve second rail.

610

AL WIRING SUCK RESTRCT 1
STR

Open load or short circuit on PWM HP fuel control block channel.

611

AL WIRING SUCK RESTRCT 2
STR

Open load or short circuit on PWM HP fuel control block channel 2.

612

AL WIRING PRESS CTRL VLV 1
STR

Open load or short circuit on PWM pressure regulating valve
channel.

613

AL WIRING PRESS CTRL VLV 2
STR

Open load or short circuit on PWM pressure regulating valve
channel 2.

615

AL EIL PROTECTION STR

Alarm for Protection Module in response to faulty or manipulated
EIL.

692

AL ECU PWR OFF ON REQ STR

ECU configuration changed, switch power off/on.

696

AL SMARTCONCT USB ERR
STR

Alarm configuration parameter.

697

AL SMARTCONCT RS485 ERR
STR

Alarm configuration parameter.

698

AL SD STOP BUTTON STR

Channel signals open load or internal error.

700

AL SD START BUTTON STR

Channel signals open load.

701

AL SD UP BUTTON STR

Channel signals open load.

702

AL SD DN BUTTON STR

Channel signals open load or internal error.

703

AL SD EXT SPEED DMD SW STR

Channel signals open load.

704

AL SD SPEED DMD INCREASE
STR

Channel signals open load or internal error.

DGC-2020HD

MTU Fault Codes