Operating power, Aem-2020 inputs and outputs – Basler Electric DGC-2020HD User Manual

Page 317

Advertising
background image

9469300990 Rev B

307

DGC-2020HD

AEM-2020

Caution

By mating conductors of dissimilar metals, galvanic corrosion could
occur which may lead to signal loss.

Connector screw terminals accept a maximum wire size of 12 AWG (3.31 mm

2

). Thermocouple

connectors accept a maximum thermocouple wire diameter of 0.177 inches (4.5 mm). Maximum screw
torque is 5 inch-pounds (0.56 N

m).

Operating Power

The Analog Expansion Module operating power input accepts either 12 Vdc or 24 Vdc and tolerates
voltage over the range of 6 to 32 Vdc. Operating power must be of the correct polarity. While reverse
polarity will not cause damage, the AEM-2020 will not operate. Operating power terminals are listed in
Table 84.

It is recommended that a fuse be added for additional protection for the wiring to the battery input of the
Analog Expansion Module. A Bussmann ABC-7 fuse or equivalent is recommended.

Table 84. Operating Power Terminals

Terminal

Description

P1-

(SHIELD)

Chassis ground connection

P1-

– (BATT–)

Negative side of operating power input

P1- + (BATT+)

Positive side of operating power input

AEM-2020 Inputs and Outputs

Input and output terminals are shown in Figure 187 and listed in Table 85.