9469300990 Rev B

337

DGC-2020HD

CEM-2020

Before returning the CEM-2020 for repair, contact the Basler Electric Technical Services Department at
618-654-2341 for a return authorization number.

Maintenance

Preventive maintenance consists of periodically checking that the connections between the CEM-2020
and the system are clean and tight.

Storage

This device contains long-life aluminum electrolytic capacitors. For devices that are not in service (spares
in storage), the life of these capacitors can be maximized by energizing the device for 30 minutes once
per year.