Generator network status display – Basler Electric DGC-2020HD User Manual

Page 57

Advertising
background image

9469300990 Rev B

47

controls are displayed at the bottom. To send a breaker open or breaker close request, select the
appropriate menu option and press Edit.
Figure 17, below, illustrates the different configurations of the one-line diagram.


Generator and Mains Breakers with Load Sensing
Generator and Mains Breakers



Generator Breaker



None

Figure 17. System Configuration One-Line Diagrams

The diagrams in Figure 17 show all breakers in the open position and all buses in a dead/unstable state.
Breaker and bus states in the diagram change in real time to reflect the actual breaker and bus status.
When a breaker is open, the line between the contacts is vertical and when closed the line is horizontal. A
stable bus is indicated by a filled rectangle and a bus in any state other than stable is indicated by an
unfilled rectangle. See Figure 18 for the different breaker and bus states.

Breaker open
Both buses dead/unstable

Breaker closed
Both buses dead/unstable

Breaker open
One bus stable and the other dead/unstable

Breaker open
One bus stable and the other dead/unstable

Breaker open
Both buses stable

Breaker closed
Both buses stable

Figure 18. One-Line Diagram Breaker and Bus States

Generator Network Status Display

The status of the generator network is available on the front panel of each DGC-2020HD when the
generator is part of a multi-machine network. The System Type setting (found in the BESTCOMSPlus

®

Settings Explorer, System Parameters, System Settings) configures the machine to be part of a multi-
machine network. When System Type is set to Multiple Generator, the machine is configured for
participation in a multiple machine system.

Generator network status is found on the front panel under Metering, Status, Gen Network Status.

G

L

G

L

G

L

P0071-90

P0071-91

DGC-2020HD

Controls and Indicators

Advertising