AEM-2020 Configuration

AEM-2020s are enabled on the Remote Module Setup screen in BESTCOMSPlus. If more than one
AEM-2020 is connected, the serial number of each module must be entered. An AEM Not Configured pre-
alarm will occur if the expected serial number does not match the serial number detected on the General
Settings, Device Info screen. The Remote Module Setup screen is illustrated in Figure 194.

Figure 194. Settings Explorer, System Parameters, Remote Module Setup

Remote Analog Inputs Configuration

Eight remote analog inputs provide metering for a variety of industrial transducers. An element can be
configured to trip when the metered input increases above or decreases below the user-defined
threshold.

The eight, identical remote analog input protection elements are designated AEM x Input #1 through AEM
x Input #8 (where x = 1 to 4). Element logic connections are made on the BESTlogic

Plus screen in

BESTCOMSPlus

® and element operational settings are configured on the AEM x Input #y (where x = 1 to

4 and y = 1 to 8) settings screen in BESTCOMSPlus.

BESTCOMSPlus Navigation Path: Settings Explorer, Programmable Inputs, Remote Analog Inputs
Front Panel Navigation Path:
Settings Explorer > Programmable Inputs > Remote Analog Inputs

Input Setup

Label Text

In order to make identification of the remote analog inputs easier, each of the inputs can be given a user-
assigned label. The label is an alphanumeric string with a maximum of 16 characters.

Hysteresis

The hysteresis setting provides a level of hysteresis between a threshold detection tripping and dropping
out. For instance, if the hysteresis is set for 5% and the threshold is set as an over threshold, once the
threshold detection trips, the measured value must drop to 95% of the threshold before the threshold
detection will drop out. This hysteresis helps prevent rapid or repeated transitions between trip and
dropout in cases where the measured input is nearly equal to a level equal to the threshold.