Trending – Basler Electric DGC-2020HD User Manual

Page 191

Advertising
background image

9469300990 Rev B

181

A pre-trigger-points setting enables a user-defined number of data points recorded prior to the event
trigger to be included in a data log. The value of this setting affects the duration of the recorded pre-
trigger points, the recorded post-trigger points, and the duration of the post-trigger points. A sample
interval setting establishes the sample rate of the data points recorded. The value of this setting affects
the pre- and post-trigger duration values and the total recording duration for a data log

Data logging is triggered by the BESTlogic™Plus DATALOGTRIGGER element. When this element
receives a TRUE input, the data logger function begins recording.

Figure 126. Settings Explorer, Report Configuration, Data Log Setup

Table 49. Settings for Data Log Setup

Locator

Setting

Range

Increment

Unit

A

Enable

Disabled or Enabled

n/a

n/a

B

Pre-Trigger Points

0 to 1,199

1

points

C

Sample Interval

5 to 12,500

5

n/a

D

Parameter 1 to 6

n/a

n/a

∗ Selectable parameters are listed in the Configurable Protection chapter.

Trending

BESTCOMSPlus

®

Navigation Path: Settings Explorer, Report Configuration, Trending

Front Panel Navigation Path: Settings > Report Configuration > Trending

The trend log records the activity of DGC-2020HD parameters over an extended period of time. When
enabled, up to six selectable parameters can be monitored over a user-defined duration ranging from 1 to
720 hours. Trend log settings are illustrated in Figure 127.

DGC-2020HD

Reporting and Alarms