Table 24. Generator Current Sensing Terminals

Terminal

Description

1 (IA+

)

A-phase generator current sensing input

2 (IA–)

3 (IB+)

B-phase generator current sensing input

4 (IB–)

5 (IC+)

C-phase generator current sensing input

6 (IC–)

Table 25. Bus Current Sensing Terminals

Terminal

Description

7 (AUX I1+)

User-programmable current sensing input 1

8 (AUX I1–)

9 (AUX I2+)

User-programmable current sensing input 2

10 (AUX I2

–)

11 (AUX I3+)

User-programmable current sensing input 3

12 (AUX I3–)

13 (AUX I4+)

User-programmable current sensing input 4

14 (AUX I4–)

Caution

Generator current sensing terminals 2 (IA–), 4 (IB–), and 6 (IC–) and
user-programmable current sensing terminals 8 (AUX I1–), 10 (AUX I2–),
12 (AUX I3–), and 14 (AUX I4–) must be terminated to ground for proper
operation.

Note

Unused current sensing inputs should be shorted to minimize noise
pickup.