257

Locator

Setting

Range

Increment

Unit

A

Unit ID

1 to 247

1

n/a

RS485

B

Unit ID

1 to 247

1

n/a

C

Response Delay

10 to 10,000

10

milliseconds

Modbus

D

Mapping

Default or Legacy

n/a

n/a

Remote Display Panel (optional)

Applications that require remote annunciation can use Basler Electric’s Remote Display Panel. This
device provides remote indication of many pre-alarm and alarm conditions.

Remote Display Panel connections are made at 62 (RDP TxD–), 61 (RDP TxD+), 49 (BATT–), and 48
(BATT+).

The following pre-alarm conditions are indicated by LEDs on the Remote Display Panel when enabled in
the DGC-2020HD:

High coolant temperature

Low coolant temperature

Low oil pressure

Low fuel level

Weak battery

Battery overvoltage‡

Battery charger failure

∗‡

The following alarm conditions are indicated by LEDs and an audible alarm on the Remote Display Panel
when enabled in the DGC-2020HD. The Overcrank, Emergency Stop, Fuel Leak/Sender Failure, and
Sender Failure alarms are always enabled.

Low coolant level

High coolant temperature

Low oil pressure

Overcrank

Overspeed

Emergency stop activated†

Fuel leak/Sender failure

∗‡

Sender failure‡

∗ The LED on the Remote Display Panel illuminates when the input that is assigned to this programmable
function is closed. This programmable function must be enabled in the DGC-2020HD.

† The LED on the Remote Display Panel illuminates when the input that is assigned to this programmable
function is closed.

‡ This LED can be reprogrammed in the DGC-2020HD to suit the needs of a particular application. The
condition listed above is annunciated by default. See the BESTlogicPlus chapter for information about
configuring the RDP Programmable Alarm and Pre-Alarm logic blocks.

Additionally, the Remote Display Panel indicates when the DGC-2020HD is not operating in Auto mode
and when the generator is supplying load. The Switch Not In Auto LED illuminates when the DGC-
2020HD is in an alarm state not listed above.

See the Terminals and Connectors chapter for more information on connecting the Remote Display Panel
to the DGC-2020HD. Refer to Basler Publication 9318100990 for more information on the Remote
Display Panel.