Pickup and Trip

When the average of the three-phase voltage (three-phase mode) or the line-to-line voltage (single-phase
mode) increases above the threshold established by the Pickup setting, a timer begins timing towards a
trip.

The duration of the timer is established by the Activation Delay. An Activation Delay of zero (0) makes the
59 element instantaneous with no intentional time delay.

If an overvoltage pickup condition persists for the duration of the element Activation Delay setting, the
element Trip output becomes true. In BESTlogicPlus, the Trip output can be connected to other logic
elements or a physical relay output to annunciate the condition and initiate corrective action.

If the pickup condition subsides before the element activation delay expires, the timer is reset, no
corrective action is taken, and the element is rearmed for any other occurrences of overvoltage.

Hysteresis

The hysteresis setting functions as an overvoltage dropout by preventing rapid switching of the pickup
output.

Per Unit

Settings which are related to machine ratings can be set in either actual units of voltage or in per unit
values. When a native unit is edited, BESTCOMSPlus automatically recalculates the per unit value based
on the native unit setting and the rated data parameter (on the System Parameters, Rated Data screen)
associated with it. Conversely, when a per unit value is edited, BESTCOMSPlus automatically
recalculates the native value based on the per unit setting and the rated data parameter associated with
it.

Once all per unit values are assigned, if the rated data parameters are changed, BESTCOMSPlus
automatically recalculates all native unit settings based on the modified rated data parameters.

The following settings have native units of Secondary Volts, and the rated data associated with them is
Rated Secondary Volts (on the System Parameters, Rated Data screen).

Overvoltage 59-x Three-Phase Pickup

Overvoltage 59-x Single-Phase Pickup

Low-Line Scale Factor

A low-line scale factor setting is used to automatically adjust the overvoltage pickup settings in
applications that might utilize more than one type of genset connection. The scale factor setting is
implemented when the DGC-2020HD is determined to be in a low-line configuration. If the Low-Line
Override function is assigned to a contact input via the Programmable Functions screen, the state of the
contact input and the detected configuration are ORed. This means, if one or both are true, then the
system is determined to be configured for low-line. The value of the scale factor setting serves as a
multiplier for the pickup settings. For example, if a scale factor contact input is received by the DGC-
2020HD and the scale factor setting is 2.000, the pickup setting will be doubled (2.000 x PU).

Alarm Configuration

An overvoltage annunciation can be user-selected to trigger a pre-alarm (warning) or alarm (shutdown). It
can also be user-configured to close a programmable output.

Element status is available in BESTlogicPlus programmable logic when “Status Only” is selected.

Logic Connections

Overvoltage element logic connections are made on the BESTlogicPlus screen in BESTCOMSPlus. The
overvoltage element logic block is illustrated in Figure 69. When the Block input is true, the 59 element is
disabled. The Trip output is true when the 59 element is in a trip condition.