Basler Electric DGC-2020HD User Manual
Page 226
216
9469300990 Rev B
Name
Description
Symbol
DEF Pre-
Severe
Inducement
This pre-alarm indicates a high level of
inducement not to operate the engine due to
low or poor quality Diesel Exhaust Fluid
(DEF), or a malfunction in the Exhaust After
Treatment System (EATS). The engine may
operate in a reduced power mode, or for a
limited time, after which it will enter a state of
severe inducement unless the problem with
the DEF or malfunction in the EATS is
corrected.
DEF Severe
Inducement
This pre-alarm indicates the highest level of
inducement not to operate the engine due to
low or poor quality Diesel Exhaust Fluid
(DEF), or a malfunction in the Exhaust After
Treatment System (EATS). The engine may
operate in a reduced power mode, or for a
limited time, or may be prevented from
starting by the ECU until the problem is
corrected. A service tool may be required to
restart the engine.
Diag Trouble
Code
True when a Diagnostic Trouble Code
exists.
DPF
Regenerate
Disabled
True when the Diesel Particulate Filter (DPF)
lamp status broadcast over CAN bus
indicates that DPF regeneration is inhibited.
DPF
Regenerate
Required
True when the Diesel Particulate Filter (DPF)
lamp status broadcast over CAN bus
indicates that DPF regeneration is required.
DPF Soot Level
High
True when the engine ECU reports via CAN
bus that Diesel Particulate Filter (DPF) soot
level is high.
DPF Soot Level
Moderately
High
True when Diesel Particulate Filter (DPF)
lamp status (yellow warning) broadcast over
CAN bus indicates that the soot level is
moderately high.
DPF Soot Level
Severely High
True when Diesel Particulate Filter (DPF)
lamp status (red warning) broadcast over
CAN bus indicates that the soot level is
severely high.
ECU Comm
Loss
True when communication to the ECU has
been lost.
Ethernet Link 1
Lost
True when Ethernet Link 1 connection is
lost.
Ethernet Link 2
Lost
True when Ethernet Link 2 connection is
lost.
Fuel Leak
Detect
True when the Fuel Leak Detect function is
configured as a pre-alarm and the activation
delay has expired.
Generator
Breaker Close
Failure
True when a generator breaker close fail
pre-alarm occurs. The pre-alarm occurs
when the DGC-2020HD has issued a
generator breaker close output but does not
receive a generator breaker status input that
indicates the breaker has closed before the
breaker close wait time has expired.
BESTlogic
™Plus
DGC-2020HD