Basler Electric DGC-2020HD User Manual

Page 258

Advertising
background image

248

9469300990 Rev B

CAN Bus 2 Address

This parameter sets a unique address number for the DGC-2020HD operating on CAN 2 (ECU). The
CAN Address is set internally by the DGC-2020HD when certain types of ECUs are selected on the ECU
Setup screen, and in this case, the user-entered value does not apply.

ECU Related Time Values - Response Timeout

This setting defines the amount of time that the DGC-2020HD will wait to receive data from the ECU
during a pulse cycle or start attempt. If no data is received during this time in a pulse cycle, a LOSS OF
ECU COMMS pre-alarm is annunciated. If no data is received in this time during an engine starting
attempt, a LOSS OF ECU COMMS alarm is annunciated.

Generator Parameter Transmit

When the Generator Parameter Transmit setting is enabled, the DGC-2020HD broadcasts generator
metered parameters over CAN as listed in Table 70. The Generator Parameter Transmit setting is not
used when ECU Type is set for MTU MDEC, MTU ECU7/ECU8, or MTU Smart Connect.

Table 70. Transmitted Generator Parameters

PGN Name

PGN

(Hex)

SPN

Parameter

Units

Scaling /

Offset

Bytes

Within

PGN
Data

Generator
Total AC
Energy

65018

(FDFA)

2468

Generator Total kW Hours
Export

kWH

n/a

1 to 4

2469

Generator Total kW Hours
Import

kWH

n/a

5 to 8

Generator
Total AC
Reactive
Power

65028

(FE04)

2456

Generator Total Reactive Power

vars

n/a

1 to 4

2464

Generator Overall Power Factor

PF

16,384

-1 offset

5 to 6

2518

Generator Overall Power Factor
Lagging

n/a

00=leading
01=lagging

10=error

11=not

available

7, bits

1 & 2

Generator
Total AC
Power

65029

(FE05)

2452

Generator Total Real Power

Watts

n/a

1 to 4

2460

Generator Total Apparent Power

VA

n/a

5 to 8

Generator
Average
Basic AC
Quantities

65030

(FE06)

2440

Generator Average L-L AC RMS
Voltage

Volts

n/a

1 to 2

2444

Generator Average L-N AC RMS
Voltage

Volts

n/a

3 to 4

2436

Generator Average AC
Frequency

Hz

128

n/a

5 to 6

2448

Generator Average AC RMS
Current

Amps

n/a

7 to 8

Communication

DGC-2020HD

Advertising