3. Installation

3−58

Festo P.BE−SPC200−EN en 0901d

Connecting the axis interface to the SPC200

Warning
Note the maximum permitted cable lengths between the
individual modules on the axis interface string and the
SPC200 (see section 3.6). Use only the following original
cables for connecting the axis interface.

Cable type

Description

KSPC−AIF−1−WD−...

Connecting cable for the first axis

KVI−CP−2−...

*)

Connecting cable for the second axis or for
I/O modules

KVI−CP−1−...

I/O modules

*)

Suitable for use as drag chain

·

Connect the axis interface for the first axis with the plug
marked IN to the 5−pin screw terminal of the power
supply module.

·

If necessary, connect the axis interface for the second axis
or modules with inputs/outputs to the OUT socket.

·

If the axis interface is at the end of an axis interface
string, install the terminating resistor type
KABS−M9−R100 on the OUT connection.

·

Fasten the plugs/sockets with the aid of the union nut in
order to prevent unintentional loosening, e.g. due to
shock.