Festo Кабели и принадлежности User Manual

Page 377

Advertising
background image

8. Diagnosis and error treatment

8−21

Festo P.BE−SPC200−EN en 0901d

Fault class 5:

Sequence control fault

Fault
stage

Fault
message

Operating status / fault explanation

Eliminating faults

C

ppp01x05

Starting program does not exist

·

Correct starting program
number or load/enter
starting program

nnn02x05

Sub−program does not exist (L command)

·

Correct NC record or load/
enter program

nnn03x05

NC record does not exist

·

Correct NC record

nnn04x05

Program no. with L command is identical to
number of the accessing program

·

Correct NC record

nnn05x05

Permitted nesting depth with L command
exceeded

·

Correct NC record

nnn06x05

Direct nominal value specification (M10) or
direct control of the valve voltage (M39)
active with new nominal value (NC comĆ
mand: G00, G01, G02, M10, M39)

·

Correct the NC record, first
conclude direct nominal
value specification or direct
control of the valve voltage
with M12.

nnn07x05

Arithmetical overrun with a register (R)

·

Correct NC record

nnn08x05

Record overrun

·

Conclude NC programs with
command M02 or M30

nnn09x05
nnn0Ax05

Reserved

zzz0Bx05

NC command cannot be processed. Either it
is not supported by the firmware or the axis
specification is not valid.

·

Check axis specification

·

Check firmware version

zzz = Additional information
yy

= Fault number

x

= Axis identifier (0 = fault is not axis−related)

ppp = Program number
nnn = NC record number of the accessing NC command

Advertising