Festo Кабели и принадлежности User Manual

Page 139

Advertising
background image

3. Installation

3−61

Festo P.BE−SPC200−EN en 0901d

3.6.2

Installation I/O function module type SPC−FIO−2E/2A−M8

Warning
Faults due to electromagnetic influences can cause fast
compensating movements of the axis. Observe the followĆ
ing installation instructions in order to avoid faults due to
electromagnetic influences.

ć

Connect the earth connection of the modules with low
impedance (short cable with large cross−sectional area)
to the earth potential.

ć

Use only the original cable type KVI−CP−2−... for connectĆ
ing the module. Fasten the plugs with the aid of the
union nut in order to prevent unintentional loosening,
e.g. due to shock.

Please note
For connecting the I/O function module you will require
the external load voltage supply module type
SPC−AIF−SUP−24V. Note the maximum permitted cable
lengths on the axis interface string (see section 3.6).

Use cable type KM8−M8−GSGD−... and plug with union nut
with M8x1 thread for connecting sensors and actuators. Seal
unused connections with the protective caps supplied. Only
in this way can you comply with protection class IP65.

Advertising