7. Description of the commands

7−54

Festo P.BE−SPC200−EN en 0901d

G61

Set positioning quality class

ć pneumatic axis; ć permitted in operating mode: Start/Stop, Record Select

Nn G61 X<Quality class> [Y.., Z.., U..]

<Quality

class >

n

Positioning quality class

n = 0 ... 6

Effect

Switches the specified axis to the set positioning quality class. Output MC_A/MC_B
or RC_A/RC_B always supplies a 1−signal when the axis fulfils the criteria of the set
positioning quality class (see following table).

Example

N005 G61 X1

N006 G00 X100

N007 G60 X

;Positioning quality class = 1, Fast stop
;Move to position 100 mm
;Exact stop without damping time

When moving to position X100, output MC_A/MC_B or RC_A/RC_B always supplies
a 1−signal when the X−axis enters the range of the positioning tolerance (fast stop
without damping time). A switch is then made to exact stop without damping time.

Remark

Command G61 has a saving effect. The positioning quality class remains effective
until a switch is made to another positioning quality class. The individual positionĆ
ing quality classes are described in the following table.
With nominal value modes 0 and 1, the set positioning quality class has no effect
(see NC command M13).