Festo Кабели и принадлежности User Manual

Page 370

Advertising
background image

8. Diagnosis and error treatment

8−14

Festo P.BE−SPC200−EN en 0901d

Fault class 1:

Initialization phase Fault in the initialization of
components and modules

Fault
stage

Eliminating faults

Operating status / fault explanation

Fault
message

A

00004x01 Actual configuration not the same as nominal

configuration (axis configuration and I/O assignment
checked)

·

Check and if
necessary correct
the configuration
of the internal
components and
string assignment
and switch the
SPC200 on again
or carry out a
System Reset.

or

·

Save the actual
configuration as
the nominal conĆ
figuration (menu
SET CONFIGUR.)
or load project
(with WinPISA)

zzz05x01

Initialization fault with an intelligent component

1)

x = 0:

Initialization fault

x = 1...4: Axis 1 (x)...4 (U)
x = 5:

Field bus module

zzz =

Location number, in ascending order from
left to right (000...003 for 4 and 000...005 for
6 locations)

·

Check stepping
motor indexer
module, subconĆ
troller or field bus
module and
switch on the
SPC200 again or
carry out System
Reset,
or

·

Servicing required

zzz06x01

The firmware versions of the basic unit and
subcontroller module are not compatible

·

Servicing required,
carry out firmware
update

zzz = Additional information
yy = Fault number
x

= Axis identifier (0 = fault is not axis−related)

1)

Stepping motor module, field bus module or axis interface module

Advertising