4. Commissioning

4−38

Festo P.BE−SPC200−EN en 0901d

Possible problems

Cause

Remedy

Remarks

The slide moves into
an end position.

The control direction is
not the same as the
direction of positioning
of the slide.

Swap the connecting
tubing on the
proportional directional
control valve.

See also appendix A

Measuring system or
measuring system cable
is defective.

Replace measuring
system or measuring
system cable

*)

Check first with
MOVEMENT TEST

The slide moves one
position.

The axis or application
data are not correct.

Correct the data

See section 6.2

The control panel
shows a fault number

See section 8.2

Eliminate fault

See section 8.2

The slide does not
move

The valve cable is
defective

Check the cable

*)

See also appendix A

No supply pressure

Switch on the
compressed air supply
or check the tubing.

See also section 3.2

The controller is
switched off because
there is no ENABLE
signal.

Apply a 1−signal to the
ENABLE input.

See also Fig. 4.2

System has stopped.

Apply a 1−signal to the
STOP input.

See also Fig. 4.2

Proportional directional
control valve is defective

Replace the
proportional directional
control valve.

*)

Check first with
MOVEMENT TEST

*)

Check and if necessary replace