Festo Кабели и принадлежности User Manual

Page 174

Advertising
background image

4. Commissioning

4−30

Festo P.BE−SPC200−EN en 0901d

8. Now apply a 1−signal to the ENABLE input in order that

the valve voltage can be modified.

During the active movement test the controller is switched off
for all axes.

9. Now specify whether you wish to raise or lower the

control voltage. Set the appropriate sign here with the
buttons

vV.

Control voltage

Direction of movement with correct
tubing

> 5 V

Negative (towards measuring system zero
point or towards the electrical connection of
the measuring system)

< 5 V

Positive

The valve voltage can be influenced with the following
buttons:

Button functions

Description

·

Press the Enter button once.

The valve voltage is increased or
reduced once by 0.01 V.

·

Press and hold down the
Enter button.

The valve voltage is increased or
reduced continuously in steps of
0.01 V.

·

Press the ESC button.

The control voltage is reset to
5.0ĂV.

In order to overcome static friction, the control voltage must
be increased or reduced accordingly.