Festo Кабели и принадлежности User Manual

Page 383

Advertising
background image

8. Diagnosis and error treatment

8−27

Festo P.BE−SPC200−EN en 0901d

Fault class 6:

Fault in positioning task or identification travel

Fault
stage

Eliminating faults

Operating status / fault explanation

Fault
message

C

nnn1Ax06 The specified reference run mode is not

permissible for this axis.

·

Correct the command

·

Check reference run mode in
the application data, comĆ
pare with that currently
being used.

Permitted:
Ĉ Stepping motor axis:

Modes 0 to 4

Ĉ Pneum. Axis:

Modes 0, 5 to 7

nnn1Bx06 The reference run for the pneumatic axis was

carried out in mode 7. Mode 0, 5 or 6 is
necessary for the desired command.

·

The reference run must be
carried out in mode 0, 5 or 6
before the command in
question.

Only the following are permissĆ
ible in mode 7:
G01, G02 and M39, see also
command G74

nnn1Cx06

Parameter outside the permitted tolerance

·

Correct NC program

zzz1Dx06

Fault in the digital nominal value specificaĆ
tion via field bus.
zzz = Fault type:
001: The nominal value transferred is

smaller than the lower software end
position.

002: The nominal value transferred is

greater than the upper software end
position.

·

Check the nominal values
generated in the field bus
master (PLC) and if necessĆ
ary adapt to the permissible
movement range.

·

Check limit values in the
application data, adapt if
necessary.

zzz = Additional information
yy = Fault number
x

= Axis identifier (0 = fault is not axis−related)

nnn = NC record number of the accessing NC command

Advertising