2 faults when positioning, Faults when positioning, 2 faults when positioning 1) drive does not move – Festo Кабели и принадлежности User Manual

Page 391: 2) axis moves against end positions

Advertising
background image

8. Diagnosis and error treatment

8−35

Festo P.BE−SPC200−EN en 0901d

8.3.2

Faults when positioning

1) Drive does not move

Cause

Remedy

Remarks

No supply pressure

Check

Valve cable is not connected
correctly

Check

See section 3.6.1

Proportional directional
control valve is defective

Check and, if necessary, replace.

Carry out movement test,
see section 4.4.2

2) Axis moves against end positions

Cause

Remedy

Remarks

Cables not connected
correctly

Check

See section A

Measuring system is
defective or not connected

Check

See section 3.6.1

Proportional directional
control valve is defective

Check

Carry out movement test,
see section 4.4.2

Tip:
Use the movement test to check the function of the measurĆ
ing system, including the transmission of measured values to
the SPC200. During the movement, at the same time observe
the actual position displayed on the MMI control panel or in
WinPISA in the status display / axes ć does the position value
change as expected?
Here you can also shift the axis by hand ć only permitted
when the compressed air is turned off!

Advertising