Festo Кабели и принадлежности User Manual

Page 376

Advertising
background image

8. Diagnosis and error treatment

8−20

Festo P.BE−SPC200−EN en 0901d

Fault class 4:

Hardware fault in the operating phase

Fault
stage

Eliminating faults

Operating status / fault explanation

Fault
message

zzz = Additional information
yy = Fault number
x

= Axis identifier (0 = fault is not axis−related)

C

zzz11x04

The AIF x has detected undervoltage on the
load voltage. The valve moves automatically
to the mid−position, the axis is no longer in
closed−loop control.
zzz = String number:
000: Concerns the 1st AIF string (on the

power supply module

100: Concerns the 2nd AIF string (on the

subcontroller module

·

Reapply load voltage and
acknowledge fault

zzz12004

A CP module has detected undervoltage on
the load voltage.
zzz = String number:
000: Concerns the 1st AIF string (on the

power supply module

100: Concerns the 2nd AIF string (on the

subcontroller module

·

Reapply load voltage and
acknowledge fault

Please note: Fault message
s0011x04 was possible also
triggered at the same time.

zzz = Additional information
yy = Fault number
x

= Axis identifier (0 = fault is not axis−related)

Advertising