8. Diagnosis and error treatment

8−16

Festo P.BE−SPC200−EN en 0901d

Fault class 4:

Hardware fault in the operating phase

Fault
stage

Fault
message

Operating status / fault explanation

Eliminating faults

C

zzz01x04

Internal system fault (Watchdog fault)
zzz = Fault type (see following description)

·

Switch system off/on again;

·

Check level and stability of
power supply

If this fault occurs again, return
for servicing

001: Fault in the switch−off phase; when the

system was switched off, certain sysĆ
tem functions (Power Down functions)
were not carried out. perhaps the
power supply module is defective

·

If necessary replace power
supply module

002: Fault whilst monitoring the power supĆ

ply during operation; unstable power
supply or environment subjected to
strong interference; or the power supĆ
ply module is defective.

·

If necessary replace power
supply module

·

If necessary eliminate interĆ
ference

003/004: Fault in monitoring the memory

range of the firmware (memory protecĆ
tion violation); environment subjected
to strong interference or basic unit is
defective.

·

Carry out Data Reset

·

If necessary eliminate interĆ
ference

·

If necessary replace basic
unit

005: Fault in monitoring the memory range

of the user programs (memory protecĆ
tion violation); environment subjected
to strong interference or basic unit is
defective.

·

Carry out Data Reset

·

If necessary eliminate interĆ
ference

·

If necessary replace basic
unit

006: Fault in accessing adaptation data The

data have not been initialized.

·

Carry out Data Reset.

zzz =

Additional information

yy =

Fault number

x

=

Axis identifier (0 = fault is not axis−related)