EAGLE 2 Operator’s Manual

Using Setup Mode • 115

Updating the Alarm Point Settings

This menu item allows you to update one or more alarm points (the reading at
which the EAGLE 2 recognizes the alarm condition).

1. From the main menu, place the cursor next to ALARM POINTS.

2. Press and release POWER ENTER RESET. The Change Alarm Point

Settings Screen appears and all detection channels are displayed.

3. Move the cursor next to the channel of the alarm point you want to

update. Press and release POWER ENTER RESET. The channel’s alarm
points are displayed (in this example for the catalytic combustible sensor
channel).

4. Move the cursor next to the alarm point or alarm operation (oxygen only)

that you want to update.

If you selected the oxygen channel, you can set the alarm rising/falling
operation in addition to the alarm points.

NOTE: If Inert Mode is active, you can change the oxygen alarm points for

both Normal Mode and Inert Mode. For more information about
changing Inert Mode alarm settings, see “Appendix N: Using the
EAGLE 2 in Inert Mode” on page 293.

CHANGE ALARM

POINT SETTINGS

> 1: CH4 2: OXY

3: H2S 4: CO

END

CH4 0- 100 %LEL

>LO ALRM : 10 %LEL

HI ALRM : 50 %LEL

LO ALRM: 5000 ppm
HI ALRM : 25000 ppm

OXY 0- 40.0 vol%

>FALLING AND RISING

LO ALRM : 19.5 vol%

HI ALRM : 23.5 vol%

END