EAGLE 2 Operator’s Manual

Specifications • 3

Specifications

Table 1: Standard Sensor Specifications

Table 2: EAGLE 2 Specifications

Combustible Gas,

Methane (CH

4

)

Calibration Standard

Oxygen (O

2

)

Hydrogen

Sulfide (H

2

S)

Carbon

Monoxide (CO)

Detection

Range

0 - 100 %LEL

0 - 40 volume%

0 - 100.0 ppm

0 - 500 ppm

Reading

Increment

1 %LEL

0.1 volume %

0.5 ppm

1 ppm

Alarm 1

Factory Setting

10 %LEL*

19.5 volume %*

5.0 ppm*

25 ppm*

Alarm 2

Factory Setting

50 %LEL

23.5 volume %

30.0 ppm

50 ppm

STEL Alarm

n/a

n/a

5.0 ppm

200 ppm

TWA Alarm

n/a

n/a

1.0 ppm

25 ppm

* When calibrating the EAGLE 2 with the Auto Calibration or the Single Calibration method, the calibration gas

value must be equal to or higher than the alarm 1 setting. See “Updating the Alarm Point Settings” on page 115
for instructions to change the alarm points if necessary for the desired calibration gas value.

Sampling

Method

Sample Draw

Response

Time

T90 Within 30 Seconds

Display Graphics

LCD

Display

Operating

Temperature

& Humidity

-20°C to 50

°

C/Below 85% RH (Without Condensation)

Indication

Accuracy

Combustible Gas (LEL), Catalytic Type Sensor
• -10°C to 40

°

C: 5% of full scale

• -20°C to 50

°

C: 6% of full scale

Combustible Gas (ppm), Catalytic Type Sensor
• ± 25 ppm or ± 5% of reading (whichever is greater)

Oxygen
• ± 0.5% O

2

Hydrogen Sulfide
• ± 5% of reading or ± 2 ppm H

2

S (whichever is greater)

Carbon Monoxide
• ± 5% of reading or ± 5 ppm CO (whichever is greater)