Carrier 17/19EX User Manual

Page 100

Advertising
background image

If the configured lead chiller does not complete the start-up before the PRESTART FAULT

TIMER (user configured value) elapses, then the lag chiller shall be started and the lead chiller

will shut down. The lead chiller then monitors the start request from the acting lead chiller to

start. The PRESTART FAULT TIMER is initiated at the time of a start request. The PRESTART

FAULT TIMER’s function is to provide a timeout in the event that there is a prestart alert

condition preventing the machine from starting in a timely manner. The timer is configured

under Lead/Lag, found in the Equipment Configuration table of the Service menu.

If the lag chiller does not achieve start-up before the PRESTART FAULT TIMER elapses,

then the lag chiller shall be stopped and the standby chiller will be requested to start, if

configured and ready.

Standby Chiller Configuration and Operation

The configured standby chiller is identified as such by having the LEAD/LAG SELECT

configured to the value of ‘‘3.’’ The standby chiller can only operate as a replacement for the lag

chiller if one of the other two chillers is in an alarm (*) condition (as shown on the LID panel). If

both lead and lag chillers are in an alarm (*) condition, the standby chiller shall default to

operate in CCN mode based on its configured Occupancy Schedule and remote contacts input.