Transferring Refrigerant from Normal Operation into the Utility Vessel

These steps describe the method of moving refrigerant from the cooler/condenser/

compressor sections into the utility vessel. This is normally performed for service work on the

cooler, condenser, or the compressor components or for long-term machine shutdown.

1. Isolate and push refrigerant into the utility vessel with the pumpout compressor.

a. Valve positions: (Blank spaces indicate open valves).

b. Turn off the machine water pumps and pumpout condenser water.

c. Turn on pumpout compressor to push liquid out of the cooler/condenser/compressor

section.

Valve

1

2

3

4

5

6

7

8

9

10

11

Condition

C

C

C

C

C

C

Click here for Figure 33 — Pumpout Unit Wiring Schematic (19EX Shown)

Click here for Figure 34 — Optional Pumpout Compressor