based on kW rate or temperature rate. It is accessed on the Equipment Configuration menu

Config screen (Table 2,

Example 5

).

9. On open-drive machines, the oil pump will be energized once every 12 hours during

shutdown periods to ensure that the shaft seal is filled with oil.

To Stop the Machine

1. The occupancy schedule will start and stop the machine automatically once the time

schedule is set up.

2. By pressing the Stop button for one second, the alarm light will blink once to confirm that

the button has been pressed, then the compressor will follow the normal shutdown

sequence as described in the

Controls

section. The machine will not restart until the CCN or

LOCAL softkey is pressed. The machine is now in the OFF mode.

Note: If the machine fails to stop, in addition to action that the PIC will initiate, the operator

should close the guide vanes by overriding the guide vane target to zero to reduce

machine load; then by opening the main disconnect. Do not attempt to stop the machine

by opening an isolating knife switch. High intensity arcing may occur.

Do not restart

the

machine until the problem is diagnosed and corrected.