Inspect starter contact surfaces for wear or pitting on mechanical-type starters. Do not

sandpaper or file silver-plated contacts. Follow the starter manufacturer’s instructions for

contact replacement, lubrication, spare parts ordering, and other maintenance requirements.

Periodically vacuum or blow off accumulated debris on the internal parts with a high-velocity,

low-pressure blower.

Power connections on newly installed starters may relax and loosen after a month of

operation. Turn power off and retighten. Recheck annually thereafter.

Never open isolating knife switches while equipment is operating. Electrical arc-
ing can cause serious injury.

WARNING

!

WARNING

CAUTION

CAUTION

!

Loose power connections can cause voltage spikes, overheating, malfunction-
ing, or failures.