A. shutdown with on/off/reset-off – Carrier 17/19EX User Manual

Page 310

Advertising
background image

LEGEND For Table 8, A - N

1CR AUX

— Compressor Start Contact

OILPD

— Oil Pressure

CA P

— Compressor Current

OILT

— Oil Sump Temperature

CDFL

— Condenser Water Flow

PIC

— Product Integrated Control

CHIL S S

— Chiller Start/Stop

PRS TRIP

— Pressure Trip Contact

CMPD

— Discharge Temperature

PSIO

— Processor Sensor Input/Output Module

CRP

— Condenser Pressure

RLA

— Rated Load Amps

ERT

— Evaporator Refrigerant Temperature

RUN AUX

— Compressor Run Contact

EVFL

— Chilled Water Flow

SMM

— Starter Management Module

GV TRG

— Target Guide Vane Position

SPR PL

— Spare Protective Limit Input

LID

— Local Interface Device

STR FLT

— Starter Fault

MTRB

— Bearing Temperature

TXV

— Thermostatic Expansion Valve

MTRW

— Motor Winding Temperature

V P

— Line Voltage: Percent

V REF

— Voltage Reference

Table 8 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages
with Troubleshooting Guides
A. Shutdown with ON/OFF/RESET-OFF

Primary Message

Secondary Message

Probable Cause/Remedy

Manually Stopped —
Press

CCN or Local to Start

PIC in OFF mode; press the CCN or local softkey to
start unit.

Terminate Pumpdown
Mode

To Select CCN or Local

Enter the Control Test table and select Terminate Lock-
out to unlock compressor.

Shutdown In Progress

Compressor Unloading

Machine unloading before shutdown due to Soft Stop
feature.

Shutdown In Progress

Compressor Deenergized

Machine compressor is being commanded to stop.
Water pumps are deenergized within one minute.

Ice Build

Operation Complete

Machine shutdown from Ice Build operation.