Example 13 — maintenance (maint04) display screen – Carrier 17/19EX User Manual

Page 299

Advertising
background image

Example 13 — Maintenance (Maint04) Display Screen

To access this display from the LID default screen:

1. Press MENU.

2. Press SERVICE.

3. Scroll down to highlight CONTROL ALGORITHM STATUS.

4. Press SELECT.

5. Scroll down to highlight MAINT04.

6. Press SELECT.

Notes:

1. Only values with capital letter reference point names are variables available for read operation. Forcing is

not supported on this maintenance screen.

2.

= delta degrees.

Table 2, Example 13 — Maintenance (Maint04) Display Screen

Description

Range/Status

Units

Reference
Point
Name

LEAD/LAG: Configuration

Current Mode

Load Balance Option
LAG Start Time
LAG Stop Time
Prestart Fault Time
Pulldown: Delta T/Min

Satisfied?

LEAD CHILLER in Control
LAG CHILLER: Mode

Run Status

Start/Stop

Recovery Start Request
STANDBY CHILLER: Mode

Run Status

Start/Stop

Recovery Start Request

DISABLE, LEAD, LAG, STANDBY, INVALID
DISABLE, LEAD, LAG, STANDBY, CONFIG
DISABLE/ENABLE
0-60
0-60
0-30
x.xx
No/Yes
No/Yes
Reset,Off,Local,CCN
Timeout,Recycle,Startup,Ramping,Running
Demand,Override,Shutdown,Abnormal,Pumpdown

Stop,Start,Retain
No/Yes
Reset,Off,Local,CCN
Timeout,Recycle,Startup,Ramping,Running
Demand,Override,Shutdown,Abnormal,Pumpdown

Stop,Start,Retain
No/Yes

MIN
MIN
MIN

DEG (

DEG C)

leadlag
llmode
loadbal
lagstart
lagstop
preflt
pull dt
pull sat
leadctrl
lagmode
lagstat

lag s s
lag rec
stdmode

stdstat

std s s
std rec