Check the cooler pressure on the LID default screen, and compare to the original holding

charge that was left in the machine. If (after adjusting for ambient temperature changes) any

loss in pressure is indicated, check for refrigerant leaks. See

Check Machine Tightness

section.

Recharge the machine by transferring refrigerant from the utility vessel. Follow the

Pumpout

and Refrigerant Transfer Procedures

section. Observe freeze-up precautions.

Carefully make all regular preliminary and running system checks. Perform a controls test

before start-up. If the compressor oil level appears abnormally high, the oil may have absorbed

refrigerant. Make sure that the oil temperature is above 150 F (66 C) or cooler refrigerant

temperature plus 70° F (39° C).

Cold Weather Operation

When the entering condenser water drops very low, the PIC can automatically cycle the

cooling tower fans off to keep the temperature up. Piping may also have to be arranged to

bypass the cooling tower as well as a tower temperature control system.

Manual Guide Vane Operation

Manual operation of the guide vanes in order to check control operation or control of the

guide vanes in an emergency operation is possible by overriding the target guide vane position.

Access the Status01 screen on the LID and highlight

TARGET GUIDE VANE POSITION

. To

control the position, enter a percentage of guide vane opening that is desired. Zero percent is