Automatic Restart After a Power Failure is not activated when a power failure occurs, and the

remote contact is closed, the machine will indicate an alarm because of the loss of voltage.

The contacts for Remote Start are wired into the starter at terminal strip TB5, terminals 8A

and 8B. See the certified drawings for further details on contact ratings. The contacts must be

dry (no power).

Spare Safety Inputs

Normally closed (NC) digital inputs for additional field-supplied safeties may be wired to the

spare protective limits input channel in place of the factory installed jumper. (Wire multiple

inputs in series.) The opening of any contact will result in a safety shutdown and LID display.

Refer to the certified drawings for safety contact ratings.

Analog temperature sensors may also be added to the options modules, if installed. These

may be programmed to cause an alert on the CCN network, but will not shut the machine down.

Spare Alarm Contacts

Two spare sets of alarm contacts are provided within the starter. The contact ratings are

provided in the certified drawings. The contacts are located on terminal strip TB6, terminals 5A

and 5B, and terminals 5C and 5D.