Common point sensor installation – Carrier 17/19EX User Manual

Page 97

Advertising
background image

Common Point Sensor Installation

Lead/lag operation does not require a common chilled water point sensor. Common point

sensors can be added to the 8-input option module, if desired. Refer to the certified drawings for

termination of sensor leads.

Note: If the common point sensor option is chosen on a chilled water system, both machines

should have their own 8-input option module and common point sensor installed. Each

machine will use its own common point sensor for control, when that machine is desig-

nated as the lead chiller. The PIC cannot read the value of common point sensors

installed on other machines in the chilled water system.

When installing chillers in series, a common point sensor should be used. If a common point

sensor is not used, the leaving chilled water sensor of the upstream chiller must be moved into

the leaving chilled water pipe of the downstream chiller.

If return chilled water control is required on chillers piped in series, the common point return

chilled water sensor should be installed. If this sensor is not installed, the return chilled water

sensor of the downstream chiller must be relocated to the return chilled water pipe of the

upstream machine.

To properly control the common supply point temperature sensor when chillers are piped in

parallel, the water flow through the shutdown chillers must be isolated so that no water by-pass

around the operating chiller occurs. The common point sensor option must not be used if water

bypass around the operating chiller is occurring.

Advertising