Calculate Minimum Load

To calculate minimum load conditions, estimate the temperature difference that the cooler

will have at 20% load, then estimate what the suction and condensing temperatures will be at

this point. Use the proper saturated pressure and temperature for the particular refrigerant

used.

Suction Temperature:

43 F (6.1 C) = 38 psig (262 kPa) saturated refrigerant pressure (HFC-134a)

Condensing Temperature:

70 F (21.1 C) = 71 psig (490 kPa) saturated refrigerant pressure (HFC-134a)

Minimum Load

T1 (at 20% Load):

2° F (1.1° C)

Minimum Load

P1:

71 – 38 = 33 psid (490 – 262 = 228 kPad)

Again, to avoid unnecessary surge prevention, add 20 psid (140 kPad) at

P1 from these

conditions:

T1 = 2° F (1.1° C)

P1 = 53 psid (368 kPad)