D. pre-start alerts, Click here for table 8d — pre-start alerts – Carrier 17/19EX User Manual

Page 313

Advertising
background image

* [LIMIT] is shown on the LID as temperature, pressure, voltage, etc., set point predefined or selected by

the operator as an override, alert, or alarm condition. [VALUE] is the actual pressure, temperature,

voltage, etc., at which the control tripped.

Table 8 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages
with Troubleshooting Guides
D. Pre-Start Alerts:

These alerts only delay start-up. When alert is corrected, the start-up will continue. No

reset is necessary.

Primary
Message

Secondary
Message

Alarm Message/Primary
Cause

Additional Cause/Remedy

Prestart Alert

Starts Limit Exceeded

STARTS EXCESSIVE Com-
pressor Starts (8 in 12 hours)

Depress the RESET softkey if addi-
tional start is required. Reasses
start-up requirements.

Prestart Alert

High Motor Tempera-
ture

MTRW [VALUE] exceeded limit
of [LIMIT]*. Check motor tem-
perature.

Check motor cooling line for proper
operation. Check for excessive
starts within a short time span.

Prestart Alert

High Bearing Tempera-
ture

MTRB [VALUE] exceeded limit
of [LIMIT]*. Check thrust bear-
ing temperature.

Check oil heater for proper opera-
tion, check for low oil level, partially
closed oil supply valves, etc. Check
sensor accuracy.

Prestart Alert

High Discharge Temp

CMPD [VALUE] exceeded limit
of [LIMIT]*. Check discharge
temperature.

Check sensor accuracy. Allow dis-
charge temperature to cool. Check
for excessive starts.

Prestart Alert

Low Refrigerant Temp

ERT [VALUE] exceeded limit of
[LIMIT]*. Check refrigerant tem-
perature.

Check transducer accuracy.
Check for low chilled water/brine
supply temperature.

Prestart Alert

Low Oil Temperature

OILT [VALUE] exceeded limit of
[LIMIT]*. Check oil temperature.

Check oil heater power, oil heater
relay. Check oil level.

Prestart Alert

Low Line Voltage

V P [VALUE] exceeded limit of
[LIMIT]*. Check voltage supply.

Check voltage supply. Check volt-
age transformers. Consult power
utility if voltage is low. Calibrate
voltage reading on STATUS01
Table.

Prestart Alert

High Line Voltage

V P [VALUE] exceeded limit of
[LIMIT]*. Check voltage supply.

Check voltage supply. Check volt-
age transformers. Consult power
utility if voltage is low. Calibrate
voltage reading on STATUS01
Table.

Prestart Alert

High Condenser Pres-
sure

CRP [VALUE] exceeded limit of
[LIMIT]*. Check condenser
water and transducer.

Check for high condenser water
temperature. Check transducer
accuracy.