* [LIMIT] is shown on the LID as the temperature, pressure, voltage, etc., set point predefined or selected

by the operator as an override, alert, or alarm contition. [VALUE] is the actual temperature, pressure,

voltage, etc., at which the control tripped.

Recycle Alert

Excessive Recycle
Starts

Excessive recycle
starts.

The machine load is too small to keep the
machine on line and there have been
more than 5 restarts in 4 hours. Increase
machine load, adjust hot gas bypass,
increase RECYCLE RESTART DELTA T.

Table 8 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages
with Troubleshooting Guides
L. Machine Alerts (Continued)

Primary
Message

Secondary
Message

Alarm Message/
Primary Cause

Additional Cause/Remedy