CONFIG TABLE CONFIGURATION SHEET

DESCRIPTION

RANGE

UNITS

DEFAULT

VALUE

RESET TYPE 1

Degrees Reset at 20 mA

–30 to 30
(–17 to 17)

DEG F
(DEG C)

10

(6)

RESET TYPE 2

Remote Temp (No Reset)

–40 to 245
(–40 to 118)

DEG F
(DEC C)

85

(29)

Remote Temp (Full Reset)

–40 to 245
(–40 to 118)

DEG F
(DEG C)

65

(18)

Degrees Reset

–30 to 30
(–17 to 17)

DEG F
(DEG C)

10

(6)

RESET TYPE 3

CHW Temp (No Reset)

0 to 15
(0 to 8)

DEG F
(DEG C)

10

(6)

CHW Temp (Full Reset)

0 to 15
(0 to 8)

DEG F
(DEG C)

0

(0)

Degrees Reset

–30 to 30
(–17 to 17)

DEG F
(DEG C)

5

(3)

Select/Enable Reset Type

0 to 3

0

ECW Control Option

Disable/Enable

Disable

Demand Limit at 20 mA

40 to 100

%

40

20 mA Demand Limit Option

Disable/Enable

Disable

Auto Restart Option

Disable/Enable

Disable

Remote Contacts Option

Disable/Enable

Disable

Temp Pulldown Deg/Min

2 to 10

3

Load Pulldown %/Min

5 to 20

10

Select Ramp Type:
Temp=0/Load=1

0/1

1

Loadshed Group Number

0 to 99

0

Loadshed Demand Delta

0 to 60

%

20

Maximum Loadshed Time

0 to 120

Min

60

CCN Occupancy Config:

Schedule Number

3 to 99

3

CCN Occupancy Config:

Broadcast Option

Disable/Enable

Disable

ICE BUILD Option

Disable/Enable

Disable

ICE BUILD TERMINATION:

0 =Temp, 1 =Contacts, 2 =Both

0, 1, 2

0

ICE BUILD RECYCLE Option

Disable/Enable

Disable

CL-5