Note: All values are variables available for read operation to a CCN. Descriptions shown with (*) support

write operations for BEST programming language, data-transfer, and overriding.

Information is applicable to hermetic machines only.

** Information is applicable to open-drive machines only.

†† Oil pressure is read directly from a differential pressure module on 17EX machines.

Entering Chilled Water
Leaving Chilled Water
Entering Condenser Water
Leaving Condenser Water
Evaporator Refrig Temp
Evaporator Pressure
Condenser Refrig Temp
Condenser Pressure
Discharge Temperature
Bearing Temperature
Motor Winding Temp

Motor Winding Hi

Temp Cutout**

Oil Sump Temperature
Oil Pressure Transducer

Oil Pressure

††

Line Voltage: Percent
Actual
*Remote Contacts Input
Total Compressor Starts
Starts in 12 Hours
Compressor Ontime
*Service Ontime
*Compressor Motor kW

–40-245 (–40-118)
–40-245 (–40-118)
–40-245 (–40-118)
–40-245 (–40-118)
–40-245 (–40-118)
–6.7-420 (–46-2896)
–40-245 (–40-118)
–6.7-420 (–46-2896)
–40-245 (–40-118)
–40-245 (–40-118)
–40-245 (–40-118)
Normal/Alarm

–40-245 (–40-118)
–6.7-420 (–46-2896)
–6.7-420 (–46-2896)
0-999
0-9999
Off/On
0-65535
0-8
0-500000.0
0-32767
0-9999

DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
PSI (kPa)
DEG F (DEG C)
PSI (kPa)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)

DEG F (DEG C)
PSI (kPa)
PSID (kPad)
%
VOLTS

HOURS
HOURS
kW

ECW
LCW
ECDW
LCDW
ERT
ERP
CRT
CRP
CMPD
MTRB
MTRW
MTRW

OILT
OILP
OILPD
V P
V A
REMCON
c starts
STARTS
c hrs
S HRS
CKW

Table 2, Example 1 — Status01 Display Screen (Continued)

Description

Range

Units

Reference Point
Name (Alarm
History)