Checking the display messages, Checking temperature sensors – Carrier 17/19EX User Manual

Page 255

Advertising
background image

Checking the Display Messages

The first area to check when troubleshooting the 17/19EX is the LID display. If the alarm light

is flashing, check the primary and secondary message lines on the LID default screen (

Figure

14

). These messages will indicate where the fault is occurring. The Alarm History table on the

LID Service menu will also carry an alarm message to further expand on this alarm. For a

complete listing of messages, see

Table 8

. If the alarm light starts to flash while accessing a

menu screen, depress EXIT to return to the Default screen to read the failure message. The

compressor will not run with an alarm condition existing, unless the alarm type is an

unauthorized start or a failure to shut down.

Checking Temperature Sensors

All temperature sensors are of the thermistor type. This means that the resistance of the

sensor varies with temperature. All sensors have the same resistance characteristics.

Determine sensor temperature by measuring voltage drop if the controls are powered, or

resistance if the controls are powered off. Compare the readings to the values listed in

Table 9A