Hot gas bypass contactor relay (3c) (optional), Oil auxiliary relay (4c), Control transformers (t1-t4) – Carrier 17/19EX User Manual

Page 56: Control and oil heater voltage selector (s1), Oil differential pressure/power supply module

Advertising
background image

Hot Gas Bypass Contactor Relay (3C) (Optional)

This relay, located in the power panel, controls the opening of the hot gas bypass valve. The

PIC energizes the relay during low load, high lift conditions.

Oil Auxiliary Relay (4C)

This relay, supplied only with open-drive machines, opens the oil cooler solenoid valve and

interlocks the oil pump with the compressor.

Control Transformers (T1-T4)

These transformers are located in the power panel and convert incoming control voltage to

either 21 vac power for the PSIO module and options modules, or 24 vac power for 3 power

panel contactor relays and a control solenoid valve.

Control and Oil Heater Voltage Selector (S1)

It is necessary to use 115 v incoming control power in the power panel. The switch must be

set to the 115-v position.

Oil Differential Pressure/Power Supply Module

This module, which is located in the control center, provides 5 vdc power for the transducers

and LID backlight.

On open-drive machines, this module outputs the difference between two pressure

transducer input signals. The module subtracts oil supply pressure from transmission sump