* [LIMIT] is shown on the LID as the temperature, pressure, voltage, etc., set point predefined or selected

by the operator as an override, alert, or alarm contition. [VALUE] is the actual temperature, pressure,
voltage, etc., at which the control tripped.

Protective
Limit

Run AUX Contact
Fault

RUN AUX Starter Contact
Fault: Check 1CR/1M aux
contacts.

Run auxiliary contact opened while
machine was running. Check starter for
proper operation.

Protective
Limit

CCN Override Stop

CHIL S S CCN Override
Stop while in LOCAL run
mode.

CCN has signaled machine to stop. Reset
and restart when ready. If the signal was
sent by the LID, release the Stop signal
on STATUS01 screen.

Protective
Limit

Spare Safety Device

SRP PL Spare Safety
Fault: Check contacts.

Spare safety input has tripped or factory-
installed jumper not present.

Protective
Limit

Excessive Motor
Amps

CA P [VALUE] exceeded
limit of [LIMIT]*. High
Amps; Check guide vane
drive.

Check motor current for proper calibra-
tion. Check guide vane drive and actuator
for proper operation.

Protective
Limit

Excessive Compr
Surge

Compressor Surge: Check
condenser water temp and
flow.

Check condenser flow and temperatures.
Check configuration of surge protection.

Protective
Limit

Starter Fault

STR FLT Starter Fault:
Check starter for fault
source.

Check starter for possible ground fault,
reverse rotation, voltage trip, etc.

Protective
Limit

Starter Overload Trip

STR FLT Starter Overload
Trip: Check amps calibra-
tion/reset overload.

Reset overloads and reset alarm. Check
motor current calibration or overload cali-
bration (do not field-calibrate overloads).

Protective
Limit

Transducer Voltage
Fault

V REF [VALUE] exceeded
limit of [LIMIT]*. Check
transducer power supply.

Check transformer power (5 vdc) supply
to transducers. Power must be 4.5 to
5.5 vdc.

Protective
Limit

Low Oil Pressure

Low Oil Pressure [OPEN]:
Check oil pressure switch/
pump and 2C aux.

Check the oil pressure switch for proper
operation. Check oil pump for proper
pressure. Check for excessive refrigerant
in oil system.

Table 8 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages
with Troubleshooting Guides
K. Machine Protect Limit Faults (Continued)

Primary
Message

Secondary
Message

Alarm Message/
Primary Cause

Additional Cause/Remedy

Excessive numbers of the same fault can lead to severe machine damage. Seek service expertise.

WARNING

!

WARNING

Advertising